1. A balance Y-connected load of ( 3 + j8 ) ohms per phase is supplied by a balanced three- phase, 60 Hz, positive phase sequence source. If VBC = 133.6998 + j159.3372 volts, determine the following: (Answers in complex numbers must be expressed in POLAR FORM) а. VAB b. VCA C. Line current lA d. Line current IB е. Line current lc f. Total real power of the load g. Total reactive power of the load 2. A TWO-WATTMETER method is used to measure the total real power of the load in Problem No. 1, where wattmeter W1 is connected in line A and W2 is connected in line C. Line B being the common tapping point of the voltage coils of W1 and W2. Determine the following: a. Reading of wattmeter W1 b. Reading of wattmeter W2 If a third wattmeter W3 is connected to line B and the two ends of the voltage coils are connected to lines C and A, what is its reading? d. If the result in Part C is multiplied by 1.732 or square root of 3, what does this value represents? С.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.52P: A balanced three-phase load is connected to a 4.16-kV, three-phase, fourwire, grounded-wye dedicated...
icon
Related questions
Question

please answer 2

1. A balance Y-connected load of ( 3 + j8 ) ohms per phase is supplied by a balanced three-
phase, 60 Hz, positive phase sequence source. If VBC = 133.6998 + j159.3372 volts,
determine the following: (Answers in complex numbers must be expressed in POLAR FORM)
а. VAB
b. VCA
С.
Line current la
d. Line current IB
e. Line current Ic
f. Total real power of the load
g. Total reactive power of the load
2. A TWO-WATTMETER method is used to measure the total real power of the load in Problem
No. 1, where wattmeter W1 is connected in line A and W2 is connected in line C. Line B
being the common tapping point of the voltage coils of W1 and W2. Determine the
following:
a. Reading of wattmeter W1
b. Reading of wattmeter W2
If a third wattmeter W3 is connected to line B and the two ends of the voltage coils are
connected to lines C and A, what is its reading?
С.
d. If the result in Part C is multiplied by 1.732 or square root of 3, what does this value
represents?
Transcribed Image Text:1. A balance Y-connected load of ( 3 + j8 ) ohms per phase is supplied by a balanced three- phase, 60 Hz, positive phase sequence source. If VBC = 133.6998 + j159.3372 volts, determine the following: (Answers in complex numbers must be expressed in POLAR FORM) а. VAB b. VCA С. Line current la d. Line current IB e. Line current Ic f. Total real power of the load g. Total reactive power of the load 2. A TWO-WATTMETER method is used to measure the total real power of the load in Problem No. 1, where wattmeter W1 is connected in line A and W2 is connected in line C. Line B being the common tapping point of the voltage coils of W1 and W2. Determine the following: a. Reading of wattmeter W1 b. Reading of wattmeter W2 If a third wattmeter W3 is connected to line B and the two ends of the voltage coils are connected to lines C and A, what is its reading? С. d. If the result in Part C is multiplied by 1.732 or square root of 3, what does this value represents?
Expert Solution
steps

Step by step

Solved in 5 steps with 5 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning