25 A 6000/500-V step down transformer takes 80 A, absorbs 500 W when 25 V is applied to the low voltage winding, the high voltage winding being short circuited. What voltage must be applied to the primary terminals when the output is 120 A at 500 V at unity pf. A. 6114 V 8.6128 V C. 6154 V D. 6272 V

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.32MCQ
icon
Related questions
Question
25.
25 A 6000/500-V step down transformer takes 80 A, absorbs 500 W
when 25 V is applied to the low voltage winding, the high voltage
winding being short circuited. What voltage must be applied to the
primary terminals when the output is 120 A at 500 V at unity pf.
A. 6114 V
8.6128 V
C. 6154 V
D. 6272 V
Transcribed Image Text:25 A 6000/500-V step down transformer takes 80 A, absorbs 500 W when 25 V is applied to the low voltage winding, the high voltage winding being short circuited. What voltage must be applied to the primary terminals when the output is 120 A at 500 V at unity pf. A. 6114 V 8.6128 V C. 6154 V D. 6272 V
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
KVL and KCL
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning