(A 100 kVA, 380 V, 50 Hz, Y-connected synchronmous generator was tested with a rated field current value of 3A and open circuit terminal voltage was measured as V₁,oc-400 V and short circuit line current was measured as Isc-220 A for this conditions. When a DC voltage of 20 V was applied to two of the terminals (between the ends of two phase coils), a current of 20 A was measured as a phase coil current. Under the given conditions, find the internal generated voltage (EA=?), stator resistance (R₁-?) and synchronous reactance (X-?) values if the field current was applied with its rated value. Be careful about your solutions to be written readable and write the answers inside the boxes as it was shown below.) EA= RA= Xs=

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.56P: Three single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit...
icon
Related questions
Question
100%
(A 100 kVA, 380 V, 50 Hz, Y-connected synchronmous generator was tested with a rated field current value of 3A and open circuit terminal voltage was measured as V₁,0c-400 V and short circuit
line current was measured as IHSC-220 A for this conditions. When a DC voltage of 20 V was applied to two of the terminals (between the ends of two phase coils), a current of 20 A was measured as a
phase coil current. Under the given conditions, find the internal generated voltage (E₁-?), stator resistance (RA-?) and synchronous reactance (XS-?) values if the field current was applied
with its rated value. Be careful about your solutions to be written readable and write the answers inside the boxes as it was shown below.)
RA
Xs=
EAF
Transcribed Image Text:(A 100 kVA, 380 V, 50 Hz, Y-connected synchronmous generator was tested with a rated field current value of 3A and open circuit terminal voltage was measured as V₁,0c-400 V and short circuit line current was measured as IHSC-220 A for this conditions. When a DC voltage of 20 V was applied to two of the terminals (between the ends of two phase coils), a current of 20 A was measured as a phase coil current. Under the given conditions, find the internal generated voltage (E₁-?), stator resistance (RA-?) and synchronous reactance (XS-?) values if the field current was applied with its rated value. Be careful about your solutions to be written readable and write the answers inside the boxes as it was shown below.) RA Xs= EAF
Expert Solution
steps

Step by step

Solved in 4 steps with 3 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning