A 3 phase, 10 kW, 400 V, connected induction 400 V, 4 pole, 50 Hz, star motor draws 20 A on full load. Its no load and blocked rotor test data are given below: No Load test: 400 V Blocked Rotor test: 90 V 6 A 15 A 1002 W 762 W Neglecting copper loss in no load test and core loss in Blocked Rotor test, estimate motor's full load efficiency.

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 6RQ: Name three factors that determine the torque produced by an induction motor.
icon
Related questions
Question

I.motor,

3 phase,
10
10 kW,
kW,
400 V, 4 pole,
50 Hz,
star
connected induction motor draws 20 A on full
load. Its no load and blocked rotor test data are
given below:
No Load test:
400 V
Blocked Rotor test: 90 V
A
6 A
1002 W
15 A 762 W
Neglecting copper loss in no load test and core
loss in Blocked Rotor test, estimate motor's full
load efficiency.
Transcribed Image Text:3 phase, 10 10 kW, kW, 400 V, 4 pole, 50 Hz, star connected induction motor draws 20 A on full load. Its no load and blocked rotor test data are given below: No Load test: 400 V Blocked Rotor test: 90 V A 6 A 1002 W 15 A 762 W Neglecting copper loss in no load test and core loss in Blocked Rotor test, estimate motor's full load efficiency.
Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Alternating Current (AC) Series Motor and Universal Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning