A refrigeration system is being designed to maintain a small frozen storage room at -5°C. The required cooling rate is 50 kW. Waste heat from the refrigeration system will be rejected to the outdoor air at 35°C. The system will be designed such that the evaporation temperature will be either -10°C or -20°C, and the condensing temperature will be either 40°C or 50°C. UAcond For the 4 possible combinations of evaporator and condenser Tcond temperatures: Apply the "rule of thumb" to estimate the cooling COP Tr Ecomp Estimate the required "size" of the evaporator heat exchange surface, UAevap Practical Refrig (W/°C) T. Estimate the required "size" of the condenser heat exchange surface, UA cond (W/°C) Tevap UAevap Show your work for Scenario A and complete the following table: Design Scenario Tevap (°C) Tcond (°C) СОР. UA evap (W/°C) UA cond (W/°C) А -10 40 В -20 40 -10 50 D -20 50

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter47: High-pressure, Low-pressure, And Absorption Chilled-water Systems
Section: Chapter Questions
Problem 13RQ: The subcooling temperature in a condenser can be measured by taking the difference between the A....
icon
Related questions
Question
A refrigeration system is being designed to maintain a small frozen storage room at -5°C. The required
cooling rate is 50 kW. Waste heat from the refrigeration system will be rejected to the outdoor air at
35°C. The system will be designed such that the evaporation temperature will be either -10°C or -20°C,
and the condensing temperature will be either 40°C or 50°C.
UA cond
For the 4 possible combinations of evaporator and condenser
Tcond
temperatures:
Apply the "rule of thumb" to estimate the cooling COP
Tn
Есотp
Estimate the required "size" of the evaporator heat exchange
Practical
Refrig
surface, UA vap (W/°C)
Estimate the required "size" of the condenser heat exchange
surface, UAcond (W/°C)
Тevap
UAevap
Show your work for Scenario A and complete the following table:
Design
Scenario
Tevap (°C)
СОР.
UA.
UA cond (W/°C)
Tcond (°C)
(W/°C)
evap
A
-10
40
В
-20
40
-10
50
-20
50
Transcribed Image Text:A refrigeration system is being designed to maintain a small frozen storage room at -5°C. The required cooling rate is 50 kW. Waste heat from the refrigeration system will be rejected to the outdoor air at 35°C. The system will be designed such that the evaporation temperature will be either -10°C or -20°C, and the condensing temperature will be either 40°C or 50°C. UA cond For the 4 possible combinations of evaporator and condenser Tcond temperatures: Apply the "rule of thumb" to estimate the cooling COP Tn Есотp Estimate the required "size" of the evaporator heat exchange Practical Refrig surface, UA vap (W/°C) Estimate the required "size" of the condenser heat exchange surface, UAcond (W/°C) Тevap UAevap Show your work for Scenario A and complete the following table: Design Scenario Tevap (°C) СОР. UA. UA cond (W/°C) Tcond (°C) (W/°C) evap A -10 40 В -20 40 -10 50 -20 50
Expert Solution
steps

Step by step

Solved in 5 steps with 1 images

Blurred answer
Knowledge Booster
Heat Exchangers
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning