You are working as an engineer a company. During an energy audit, you realize that your company has a 40 kw transformer that is connected all the time. While inspecting the transformer, you calculate the core losses from the device to be approximately 5% of its rated capacity. Assume that the electrical costs are 10 C/kWh and 10 USD/KW/month of peak demand, that the average building use is 12 h/month, and that the average month has 720 hours. Estimate the annual cost savings from installing a switch that would energize the transformer only when the building was being used. The transformer is used h/month, and it can be turned off for the remaining of the month. That is h/month. That means the transformer can be turned off for h/year. The core losses from the tansformer is kW. Installing a switch to turn on the transformer only when the building is used results: Annual energy savings of kWh/year. Annual cost savings of USD/year. Does it make sense to use this strategy?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.57P: A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when...
icon
Related questions
Question
You are working as an engineer a company. During an energy audit, you realize that your company has a 40 kW transformer that is connected all the time. While
inspecting the transformer, you calculate the core losses from the device to be approximately 5% of its rated capacity. Assume that the electrical costs are 10 C/kWh
and 10 USD/kW/month of peak demand, that the average building use is 12 h/month, and that the average month has 720 hours. Estimate the annual cost savings
from installing a switch that would energize the transformer only when the building was being used.
The transformer is used
h/month, and it can be turned off for the remaining of the month. That is
h/month.
That means the transformer can be turned off for
h/year.
The core losses from the tansformer is
kW.
Installing a switch to turn on the transformer only when the building is used results:
Annual energy savings of
kWh/year.
Annual cost savings of
USD/year.
Does it make sense to use this strategy?
Transcribed Image Text:You are working as an engineer a company. During an energy audit, you realize that your company has a 40 kW transformer that is connected all the time. While inspecting the transformer, you calculate the core losses from the device to be approximately 5% of its rated capacity. Assume that the electrical costs are 10 C/kWh and 10 USD/kW/month of peak demand, that the average building use is 12 h/month, and that the average month has 720 hours. Estimate the annual cost savings from installing a switch that would energize the transformer only when the building was being used. The transformer is used h/month, and it can be turned off for the remaining of the month. That is h/month. That means the transformer can be turned off for h/year. The core losses from the tansformer is kW. Installing a switch to turn on the transformer only when the building is used results: Annual energy savings of kWh/year. Annual cost savings of USD/year. Does it make sense to use this strategy?
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning