Q2. Two relays R₁ and R₂ are connected in two sections of a feeder as shown in Figure-2. The CTS ratio 1000:5 Amp. The plug setting of relay R₁ is 100% and R₂ is 125%. The operating time characteristic of the relays is given in table: Plug Setting Multiplier (PSM) Operating Time in Seconds 1000/5A 1x port Relay R2 4 5 4 The time multiplier setting (TMS), of the relay R₁ is 0.3. The time grading scheme has a discriminative margin of 0.5s between the relays. A 3-phase short circuit fault after relay R₁ results in a fault current of 5000A. Find the actual operating times of R₁ and R₂. What is the time multiplier setting of R₂? B 2 10 5 1000/5A * foot 8 3 Relay R1 Figure-2: System network 10 20 2.8 2.4 5000 A

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 8RQ
icon
Related questions
Question
Q2. Two relays R₁ and R₂ are connected in two sections of a feeder as shown in Figure-2. The
CTS ratio 1000:5 Amp. The plug setting of relay R₁ is 100% and R₂ is 125%. The operating time
characteristic of the relays is given in table:
Plug Setting Multiplier (PSM)
Operating Time in Seconds
1000/5A
1x port
Relay
R2
2
10
B
4
5
The time multiplier setting (TMS), of the relay R₁ is 0.3. The time grading scheme has a
discriminative margin of 0.5s between the relays. A 3-phase short circuit fault after relay R₁
results in a fault current of 5000A. Find the actual operating times of R₁ and R₂. What is the time
multiplier setting of R₂?
1000/5A
* foot
5
4
Relay
R1
Figure-2: System network
8
3
10
20
2.8 2.4
5000 A
Transcribed Image Text:Q2. Two relays R₁ and R₂ are connected in two sections of a feeder as shown in Figure-2. The CTS ratio 1000:5 Amp. The plug setting of relay R₁ is 100% and R₂ is 125%. The operating time characteristic of the relays is given in table: Plug Setting Multiplier (PSM) Operating Time in Seconds 1000/5A 1x port Relay R2 2 10 B 4 5 The time multiplier setting (TMS), of the relay R₁ is 0.3. The time grading scheme has a discriminative margin of 0.5s between the relays. A 3-phase short circuit fault after relay R₁ results in a fault current of 5000A. Find the actual operating times of R₁ and R₂. What is the time multiplier setting of R₂? 1000/5A * foot 5 4 Relay R1 Figure-2: System network 8 3 10 20 2.8 2.4 5000 A
Expert Solution
steps

Step by step

Solved in 6 steps with 4 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning