Question
Book Icon
Chapter 12, Problem 12.1PFS
To determine

The LRFD design tensile strength and the ASD allowable tensile strength for given members.

Expert Solution & Answer
Check Mark

Answer to Problem 12.1PFS

The LRFD design tensile strength is 219.1k .

The ASD allowable tensile strength is 146.1k .

Explanation of Solution

Given:

  size of plates=1"×16"yield strength of steel,Fy=36ksiultimatetensilestrengthFu=58ksiBoltsize=78in

Formula used:

  Rn=Fnv×Ab×numberofboltswhere,Rnistheshearingstrength of boltsFnvisthenominalstrengthinbearingtypeconnectionAbisthearea of bolts

Given that the A325, 78in a bolt is used.

Calculate the area of the bolt as follows:

  Ab=π4d2=π4782=0.60132in2

From table 12.5, Fnv=54ksi

The shearing strength of the bolt is given by,

  Rn=Fnv×Ab×numberofbolts=54×0.60132×9=292.2k

By LFRD design, the tensile strength is given as,

  Rn'=ϕRn=0.75×292.2=219.1k

Hence, the tensile strength of LFRD is 219.1k

By ASD design, the allowable tensile strength is given by,

  Rn'=RnΩ=292.22=146.1k

Hence, the allowable tensile strength by ASD design is 146.1k

Conclusion:

The tensile strength by LFRD is 219.1k and the allowable tensile strength by ASD design is 146.1k

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
Q14 What is the available tensile strength of a WT 20x74.5 made of A572 grade 50 steel? Use ASD, assume a shear lag factor (U) of 0.75, the connections are welded, and neglect block shear or other Chapter J requirements. Check both yielding and rupture. a) 800 kips b) 986 kips c) 533kips d) 656 kips
A 3/4 in (thickness) X 5 in (height) steel plate is connected to another one through two bolts of nominal diameter 1/2 in in a zig-zag arrangement as shown. Determine the tensile strength capacity Pu of the connection. Review the three limit-states: (a) yielding in the gross area, (b) rup- ture in the overall net tensile area, and (c) block shear strength.
Question 1 Check that the medium-term load of 38 kN applied to the spaced column shown in below complies with the design requirements of BS 5268-2. The column consists of two 38 x 150 C22 timbers 76 mm apart. All joints are glued and intermediate packs are 250 mm long. suitable connection #### x ->89² 6:38. Y T -end blocking AP 100 intermediate blocking L₂ 1₁ x W L W EFH 400 m 38kN medium term load -ICHICHID -200 600 600 600 600 600 600 200 38kN medium term load
Knowledge Booster
Background pattern image
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Steel Design (Activate Learning with these NEW ti...
Civil Engineering
ISBN:9781337094740
Author:Segui, William T.
Publisher:Cengage Learning